When using a variable frequency drive (VFD), how are the starting current and starting torque of the motor?
Using a frequency converter for operation, the frequency and voltage increase correspondingly with the acceleration of the motor, and the starting current is limited to below 150% of the rated current (depending on the model, it can be 125% to 200%). When starting directly with a power frequency supply, the starting current is 6 to 7 times higher, which can cause mechanical and electrical shocks. Using a frequency converter allows for a smooth start (the starting time is extended). The starting current is 1.2 to 1.5 times the rated current, and the starting torque is 70% to 120% of the rated torque; for frequency converters with automatic torque boost function, the starting torque can exceed 100%, allowing for full load starting.